CONTROL STRATEGY · S1 / S2

System Mode

DB LIVE
CURRENT TIME--:--:--
DEVICE NETWORK Gateway Status
11 ESP · realtime 1s
Weather WS-MOD-01
OFFLINE
Actuator ACT-MOD-01
OFFLINE
Mainboard L3 MB-L3-01
OFFLINE
Mainboard L5 MB-L5-01
OFFLINE
Remote AC AC-REMOTE-01
OFFLINE
PZEM 01 PWR-01
OFFLINE
PZEM 02 PWR-02
OFFLINE
PZEM 03 PWR-03
OFFLINE
PZEM 04 PWR-04
OFFLINE
PZEM 05 PWR-05
OFFLINE
PZEM 06 PWR-06
OFFLINE
RESEARCH SCENARIO

S2 · REACTIVE RULES

Reactive cascade: E_wp VISUAL → THERMAL-FACADE → AC-BALANCE.

ACTIVE STAGE VISUAL_SENSOR_UNAVAILABLE Workplane illuminance E_wp unavailable.
RESEARCH MODE

S1 / S2 Selection

MANUAL bukan skenario penelitian. Gunakan tombol PAUSE ENGINE sebelum melakukan commissioning manual pada halaman Actuator / AC Control.

CONTROL ENGINE

PAUSED

PAUSED
DRY RUN ON
LAST CYCLE 14:23:33
DRY RUN aktif: rules dan Decision Log berjalan, tetapi command actuator / AC tidak dikirim.
CONTROLLER READINESS

Sensor & Calibration

FIN CALIBRATION NOT READY 90° / 107° / 147° → target 0–100%
E_wp WORKPLANE NOT READY 0 fresh channels
TEMPERATURE NOT READY 0 fresh channels
RADIATION WEST NOT READY
RADIATION NORTH NOT READY
LIVE INPUT

Intervention Room

E_wp AVG
INDOOR TEMP
AC SETPOINT
S2 PARAMETERS

Reactive Thresholds

E_wp target350 lux
E_wp hard floor250 lux
E_wp lower hysteresis300 lux
E_wp upper hysteresis400 lux
Thermal band22.5–26.5 °C
Observe window10 min
AC clamp24–27 °C